22
Dichtung
Z-Profil
Holzbretter
(min. 30 mm)
The storage room must be periodically cleaned of fine particle
deposits. Appropriate accessibility must therefore be provided.
BEARING VENTILATION
Carbon monoxide (CO) may be released during storage of the
pellets. This is a non-irritating, toxic gas which is colourless,
odourless and tasteless. Odours can be caused by the release of
volatile hydrocarbons (VOC).
In order to be able to enter the pellet store safely at all times,
constant ventilation of the room must be ensured. This can be
done with the help of ventilating covers. These must be fitted to
both the filling and the extraction nozzles. Before entering the
warehouse, it should be well ventilated for at least 15 minutes. It
is very important to enter the pellet store only in the company
of a second person, who should be outside the danger zone
for safety reasons. The pellet store should not be entered for
four weeks after filling. If this is nevertheless necessary, the CO
content should be measured beforehand, e.g. with a mobile CO
warning device. A store buried underground as well as a pellet
store with a content of more than 15 tonnes must always be
entered with a CO warning device attached to the body.
Stickers with these safety instructions must be placed in a clearly
visible position at the entrance to the storage facility.
DIN EN ISO 20023 and VDI Guideline 3464 regulate the
ventilation of pellet stores.
6.4 MAINTENANCE
PLANING FOLDER PELLET BOILER
DETAIL DOOR
For storage quantities ≤ 15,000 kg, there are no fire protection
requirements for doors or hatches to the pellet store. Doors
and hatches must open outwards and be fitted with a
circumferential seal (dust-tight). For doors or hatches to the
pellet store, wooden boards must be fitted on the inside to
relieve pressure so that the pellets do not press against the door
or hatch. The door handle must be removed from the inside.
The door lock must be sealed dust-tight from the inside.
ATTENTION:
Observe country-specific
regulations!
DETAIL IMPACT PROTECTION MAT
The impact protection mat (1000x1250 mm) protects the
pellets against from breaking when they hit the storage room
wall. Furthermore, the wall itself is protected from damage.
The impact protection mat consists of an abrasion-resistant
and ageing-resistant plastic with a fastening option for ceiling
mounting and a downward tensioning option (trampoline
eect). It is mounted opposite the filling spout.
6.5 FLOOR PLAN/SECTION PELLET STORAGE ROOM
min. 200
Wooden boards
Impact mat
Door
(see detailed view)
Screw discharge
Inlet & outlet spigots
Storz “A“
min. 500
min. 300
All dimensions in mm!
ATTENTION:
The distance between the wall and the impact
mat must be at least 300 mm!