Security Functions
315
1070 073 822-104 (02.06) GB
Enable Voltage Control
When this checkbox is activated, internal supply voltages are monitored. In
the event of an error, the green LED Vout extinguishes and the following
message is generated and distributed throughout the system: Board Volt-
age failure! Check System!.
Disable Auto Power Off
CAUTION
Loss of data!
Activation of this checkbox no longer makes a safe shutdown poss-
ible in the event of a power failure. The device switches off instantly!
This option disables both the USP monitoring function and the power-off
delay for the power supply:
D A voltage interruption will cause the PC to shut down immediately.
D After a normal shutdown, the wait interval of approx. 60 seconds prior to
the shutdown of the power supply is omitted.
Although this function reduces the wait times during startups and software
installations, it must always be disabled during standard operation!
No Powerdown on Shortbreak
When this checkbox has been activated, interruptions in the power supply of
up to 5 seconds are permitted without affecting ongoing operations. Only in
the case of power interruptions lasting in excess of 5 seconds will the UPS
logic be started and the safe shutdown of the system initiated.
Command
This dialog box provides for the linking and activation of an executable pro-
gram (*.exe; *.bat) which is to be started and executed after the initilaization
of the shutdown. This is helpful in situations where applications failing to re-
spond to the systemwide messagesmust be backed up and terminated. To
this end, appropriate housekeeping and termination programs can be en-
tered and activated in this dialog. If there are several programs, or if the pro-
grams require transfer parameters, they must be combined in a batch file
and then entered.
. The entry itself may not contain any invocation parameters, and the de-
clared program itself must not initiate a shutdown!