Security Functions
3–16
1070 073 822-104 (02.06) GB
Default button
Selecting this button returns all settings to their default values.
These are:
D COM port: COM4
D Shutdown Delay Time: 30 sec
D Enable Startup Battery Test: enabled
D Enable Temp Control: enabled
D Enable Fan Control: enabled
D Enable Voltage Control: enabled
D Disable Auto Power Off: disabled
D No Powerdown on Shortbreak: enabled
D Execute Command File: disabled
Health Monitor
This dialog section indicates the current readings for internal voltages, bat-
tery voltage, system temperature and fan functions.
The Battery Voltage reading is updated only after a battery test. The battery
test occurs automatically after a system start, and in 12-hour intervals there-
after; it can also be initiated by pressing the Test Battery button.
D The LED illuminates red when the voltage reading of the battery voltage
measured under load is low.
D The LED illuminated green when the battery pack is fully functional.
. Excessive repetitions of the battery test will discharge the battery
pack. Never perform more than 5 battery tests within a 24-hour period.
The following applies to Fan Speed monitoring:
D Red LED: Fan at standstill, or fan speed is too low or too high.
D Green LED: Fan is working properly.
Pressing the StopAutoRefresh button disables the automatic updating of
measured readings, and the legend on the button changes to AutoRefresh.
Pressing the AutoRefresh button again enables automatic measurement
updating, again changing the legend on the button to StopAutoRefresh.
Info
Shutdown Count
The displayed value shows how often the system was shut down by UPS, i.e.
how many charging cycles the battery has been subjected to. More details
regarding after how many charging cycles it is necessaary to replace the re-
chargebale batteries is contained in section 8.2.3.
. Windows NT stores all important events under the following:
VERWALTUNG " EREIGNISANZEIGE " PROTOKOLL/ANWENDUNG