EasyManua.ls Logo

Bosch FHP560 - 11.8 STRAIGHT COOL + ECONOMIZER

Bosch FHP560
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Applications Manual FHP560 Controller | 19
Bosch Thermotechnology Corp.
Data subject to changePage____ of ____
11.8 STRAIGHT COOL + ECONOMIZER
UNIT TERMINAL BLOCK
TO BACnet
MS/TP
NETWORK
LWTS
STANDARD COMPONENTS:
DATS - DISCHARGE AIR TEMPERATURE SENSOR
LWTS - LEAVING WATER TEMPERATURE SENSOR
EWTS - ENTERING WATER TEMPERATURE SENSOR
REFER TO UNIT WIRING DIAGRAM FOR FURTHER DETAILS
EWTS
DATS
FHP560
RED
GREEN
WHITE
BLACK
TERMINATION DETAIL
RNET: SENSORS
Heat Pump Sequence of Operation – STRAIGHT COOL + ECONOMIZER
Supply Fan Start/Stop:
The supply fan will be started according to the schedule. After the supply fan has been started the control sequence will be enabled.
Zone Control:
The compressor will cycle to maintain the zone temperature at setpoint.
Straight Cool Control:
Unit is con gured for mechanical cooling only and the reversing valve is not installed. BO-2 is disabled and unused.
Night Setback:
When in “unoccupied”, the unit will cycle as necessary to maintain the night setback zone temperature at setpoint.
Shutdown:
When the unit is shutdown by either a stop command or system safety the unit will be set as follows:
Supply fan will be on (user configurable)
Compressor(s) will be off
Economizer:
Water Side Economizer (WSE) option must be con gured by the equipment integrator. A factory installed Entering Water Temperature (EWT)
sensor in IN-5 (IN-2 if IEM is present) is used to enable the economizer mode during cooling operations.
Entering water temperature values below 55°F (user con gurable) will enable economizer mode.
A 3-way economizer valve is required for the WSE option and is connected to BO-5.
HEAT PUMP
Point Name
Hardware Points Software Points
Show On
Graphic
AI AO BI BO AV BV Sched Trend Alarm
Zone Temperature X X X X
Heating Setpoint X
Cooling Setpoint X
Supply Fan Command X
Compressor Stage 1 Output X
Compressor Stage 2 Output X
Reversing Valve Command
Occupied Command X X X X
Discharge Air Temperature X
Leaving Water Temperature X
Entering Water Temperature X
Economizer Valve Output X
Condensate Over ow X
Lockout Alarm X
Schedule
Totals
4014311122
Total Hardware Total Software
982
Table 16

Related product manuals