Panel Controller Isolate | en 59
Bosch Sicherheitssysteme GmbH User Guide 2017.09 | 7.0 | F.01U.258.929
13 Isolate
This chapter contains information about the following points:
– Isolating and de-isolating elements, page 59
– Displaying list of all isolated elements, page 59
Caution!
Bypassed detectors: Alarm messages from bypassed detectors are no longer displayed, only
faults.
Isolated detectors: Isolated detectors are not analyzed.
13.1 Menu overview
Bypass
Block
-> Bypass Show blocked devices Select by
number
Block Group Printer
Block -> Sounder Strobe HVAC Doorholder
Transmission device Detector Extinguishing
system
Annunciator
Logical zone More... -> Control
element
Interface
module
13.2 Isolating and de-isolating elements
Select the element you require in the submenu.
Example:
To isolate a detector, select the following in the start menu:
1. Bypass Block
2. Block
3. Detector
Various selection criteria are displayed. See also Working with lists, page 26.
4. Select a selection criterion, e.g. By description.
A list of the detectors is displayed. Refer to Scrolling through lists, page 27 for information
on how to scroll forward and backward through the list.
5. Select the required list fields.
The list fields are marked.
6. Select Block.
The selected elements are isolated.
To de-isolate the elements again, repeat all previous steps but select Un- block in step 6.
C
A C after a detector means that this detector is part of a closed group and cannot be isolated
individually. In order to isolate a detector marked in this way, please select Logical zone in
step 3.
13.3 Displaying list of all isolated elements
There are two ways to display a list of all isolated elements:
– Using the menu, page 60
– Via the status bar, page 60