Plena Voice Alarm System | Software Manual | Action Programming en | 36
7.2.4 Business trigger
7.2.4.1 Overview
See figure 7.8 for an overview of the Business trigger
tab. On this tab, the actions of the business triggers of
the voice alarm controller can be programmed.
• Each business trigger input is programmed with
individual settings via the Message, Select Zone and
Priority drop-down lists (see section 7.2.4.2).
• All business trigger inputs are programmed via the
drop-down list at the bottom of the tab (see section
7.2.4.3).
7.2.4.2 Individual business trigger settings
Proceed as follows for each business trigger input:
1 Select the pre-recorded message from the Message
drop-down list to play when input 1 is activated.
2 Select the zones to where the message plays from the
Select zone drop-down list for input 1.
3 Select the priority of the message from the Priority
drop-down list for input 1.
4 Repeat steps 1 to 3 for the inputs 2 to 6.
5 Click the Save button to save the changes.
7.2.4.3 General settings
Proceed as follows:
1Select Action to set the condition when a trigger is
made active.
• If Close is selected, the trigger is made active
when the circuit is closed.
• If Open is selected, the trigger is made active
when the circuit is open.
2 Select Type to set the condition for when a trigger
signal stops.
• If Momentary is selected, the trigger is active
until the signal stops.
• If Toggle is selected, the trigger is active until a
second signal is made.
3Click the Save button to save the changes.
7.2.5 Mic/line input
See figure 7.9 for an overview of the Mic/line input tab.
On this tab, the action of the mic/line input with VOX
functionality of the voice alarm controller can be
programmed.
Proceed as follows:
1 Select the priority of the mic/line input with VOX
functionality of the voice alarm controller from the
Priority drop-down list (2 - 14).
2 Select the zone or zone group to which the audio of
the mic/line input with VOX functionality of the
voice alarm controller must be distributed from the
Select zone drop-down list.
3Click the Save button to save the changes.
figure 7.8: Business trigger
figure 7.9: Mic/Line input tab