PRAESENSA Programming options | en 137
Bosch Security Systems B.V.
Underwriters Laboratories Listing Document (ULLD)
2021.12.21 | V0.15b | F.01U.402.882
6.4.5 Zone definitions
On the Zone definitions pages, the amplifier output channels and zone routing can be defined.
It is possible to configure:
6.4.6 Call definitions
Using the Call definition page, call definitions can be defined.
Call definitions are used to make announcements, are custom made, and could contain several
characteristics as shown in the table following. To do so:
Topic
Configure /
programming
Feature or option Permitted
in UL2572
(Y/N/
required)
Possible settings Value Settings
permitted in
UL2572
Call definitions
(Configuring /
definition of
announcements
/ calls.)
Call definitions Yes Priority Selection (32‑255) > 224 for
emergency
use. Other
values for
Ancillary
function
Required Alarm Selection (None /
Emergency
Set for
Emergency in
case priority
is > 224
Yes Start tone Selection A start tone
fit for the
intended
purpose
Yes Attenuation of start tone Selection (0 dB‑20
dB)
Make sure
speech
intelligibility
is sufficient
Yes Messages Selection One or more
messages or
tones fit for
the intended
purpose
Yes Attenuation of message Selection (0 dB‑20
dB)
Make sure
speech
intelligibility
is sufficient
Yes Repetitions Selection (0‑10/
Infinite)
The number
of repetitions
fit for the
intended
purpose
Only Infinite
is allowed.