80 en | Installation wiring PRAESENSA
2021.12.21 | V0.15b | F.01U.402.882
Underwriters Laboratories Listing Document (ULLD)
Bosch Security Systems B.V.
3.7.13 Technical data
Electrical
Power transfer
Mains power supply input
Rated input voltage range
Frequency range
Maximum input current
120VRMS
60Hz
10A
Battery power supply input
Nominal DC input voltage
Maximum current
Under-voltage protection
12V
90A
<9V
Battery charger
Nominal charging current
Maximum charging current
Nominal float voltage
8.5A
8.8A
13.5V
Regulated 24VDC output
Nominal DC output voltage
Maximum continuous current
Maximum peak current
24V
0.7A
0.9A
Power over Ethernet (PoE 1‑2)
Nominal DC output voltage
Standard
Maximum PD load
48V
IEE802.3af (mode B)
12.95W
Power consumption
Mains powered
Active mode, all outputs loaded
Battery powered
Active mode, all outputs loaded
<1000W
<1000W
Control interface
Control input contacts (1-8)
Principle
Galvanic isolation
Minimum hold time
Maximum voltage to ground
Contact closure
No
100ms
24V
Control output contacts (1-8)
Principle
Galvanic isolation
Maximum contact voltage
Maximum contact current
Maximum voltage to ground
Contact switch over
(Relay SPDT)
Yes
110VDC, 125VAC
1A
500V