44 en | Installation wiring PRAESENSA
2021.12.21 | V0.15b | F.01U.402.882
Underwriters Laboratories Listing Document (ULLD)
Bosch Security Systems B.V.
3.4.9 Technical data
Electrical
Amplifier outputs
Rated output voltage
100V mode, 1kHz, THD <1%, no load
70V mode, 1kHz, THD <1%, no load
100VRMS
70VRMS
Maximum continuous audio power during Alarm and
normal standby condition:
All channels combined
100V mode, load 66.7ohm
70V mode, load 33.3ohm
Channel1
100V mode, load 66.7ohm
70V mode, load 46.7ohm
Other channels
100V mode, load 133.3ohm
70V mode, load 66.7ohm
150W
150W
150W
105W
75W
75W
Power transfer
Power supply input A/B
Input voltage 48VDC
Maximum current consumption 7A
Supervision
End‑of‑Line detection mode Pilot tone
25.5kHz, 3VRMS
Power supply input A/B Undervoltage
Ground short detection (loudspeaker lines) <50kohm
Amplifier channel redundancy switching Internal spare channel
Amplifier short circuit ≤ 500mohm
Loudspeaker field wire class ClassA, ClassB, Dual ClassB.
Network interface
Ethernet
Protocol
Redundancy
100BASE‑TX,
1000BASE‑T
TCP/IP
RSTP ClassN
Ports 2
This product is intended for dry indoor use only.