EasyManua.ls Logo

Bosch PRAESENSA - Technical Data

Bosch PRAESENSA
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
44 en | Installation wiring PRAESENSA
2021.12.21 | V0.15b | F.01U.402.882
Underwriters Laboratories Listing Document (ULLD)
Bosch Security Systems B.V.
3.4.9 Technical data
Electrical
Amplifier outputs
Rated output voltage
100V mode, 1kHz, THD <1%, no load
70V mode, 1kHz, THD <1%, no load
100VRMS
70VRMS
Maximum continuous audio power during Alarm and
normal standby condition:
All channels combined
100V mode, load 66.7ohm
70V mode, load 33.3ohm
Channel1
100V mode, load 66.7ohm
70V mode, load 46.7ohm
Other channels
100V mode, load 133.3ohm
70V mode, load 66.7ohm
150W
150W
150W
105W
75W
75W
Power transfer
Power supply input A/B
Input voltage 48VDC
Maximum current consumption 7A
Supervision
End‑of‑Line detection mode Pilot tone
25.5kHz, 3VRMS
Power supply input A/B Undervoltage
Ground short detection (loudspeaker lines) <50kohm
Amplifier channel redundancy switching Internal spare channel
Amplifier short circuit ≤ 500mohm
Loudspeaker field wire class ClassA, ClassB, Dual ClassB.
Network interface
Ethernet
Protocol
Redundancy
100BASE‑TX,
1000BASE‑T
TCP/IP
RSTP ClassN
Ports 2
This product is intended for dry indoor use only.