138 en | Programming options PRAESENSA
2021.12.21 | V0.15b | F.01U.402.882
Underwriters Laboratories Listing Document (ULLD)
Bosch Security Systems B.V.
Topic
Configure /
programming
Feature or option Permitted
in UL2572
(Y/N/
required)
Possible settings Value Settings
permitted in
UL2572
Yes Live speech Selection Yes/No Yes for use
for live
speech pages
Yes Attenuation live speech Selection (0
dB‑20dB)
Make sure
speech
intelligibility
is sufficient
Yes End tone Selection A end tone fit
for the
intended
purpose
Yes Attenuation of end tone Selection (0
dB‑20dB)
Make sure
speech
intelligibility
is sufficient
Yes Continue call Selection: No/After
interruption
Set to “After
interruption”
for
emergency
use
Yes Audio input Selection: <Default>/
input
An audio
input for the
intended
source.
Select
<Default> for
ACU/LOC use
6.4.7 Action definitions
On the Action definitions pages specific device functionality can be configured, e.g. the
buttons of the call station (extension), control inputs of the multifunction power supply and
the virtual control inputs of the system controller.
System controller
On the Action definitions page of the system controller, the virtual control inputs could be
defined, which could be used by the Open Interface.
Multifunction power supply
On the Action definitions page of the Multifunction power supply the Control inputs and
control outputs could be defined.