158 en | System Configuration PRAESENSA
2021.12.21 | V0.15b | F.01U.402.882
Underwriters Laboratories Listing Document (ULLD)
Bosch Security Systems B.V.
12 Remote Annunciator
13 Paging station - First responder panel (PRA-
FRP3-US )
See
First responder panel | PRA-FRPx-US, PRA-
FRPx-USNY, page 108
.
Notice!
Items 4 and 13 must be mounted next to each other if no fire annunciator is available or if the
control of the fire system is available on the FACP or if there are no control buttons (Silence /
Reset) on the fire annunciator.
Notice!
The FACP (item 4) and NAC (item 2) need to be able to support 15minutes Alarm after 24h
of standby. This is required for new and retrofit applications.