6.6 Digital and Relay Output
Code Name Setting Range Default Min. Attri.
F2.36 DO1 output 0: No function assigned from ASF
1: Converter warning
2: Green CytroPac flashing LED
3: Red CytroPac flashing LED
4: Oxygen too high (for myCro)
5: Pressure too low (for myCro)
1 - Run
F2.37 EDO output 0 - Run
F2.38 EDO2 output
0: No function assigned from ASF
1: Converter warning
2: Green CytroPac flashing LED
3: Red CytroPac flashing LED
4: Oxygen too high (for myCro)
5: Pressure too low (for myCro)
6: Degas/gas valve control (for my-
Cro)
0 - Run
F2.40 Relay 1 output 0: No function assigned from ASF
1: Converter warning
2: Two points / double pump control
0 - Run
F2.41 Extension relay output 0 - Run
Tab. 6-7: Parameter list of digital and relay output
The FcP 5020 default setting of DO1 is ''1'', i.e. the frequency converter warning.
Meanwhile the default setting of relay and EDO / EDO2 when connected to ASF
are both ''0'', which means the function of relay and EDO / EDO2 is assigned by
EFC firmware.
The EFC parameter E2.15 has been set to ''14'' (frequency converter error) by
ASF as FcP default setting. For more EFC parameter changed as FcP default set-
ting, please refer to chapter 8.6 "Auto-modified EFC Parameters in FcP Initializa-
tion" on page 74.