7.10.3 Actual Pressure Monitoring
Code Name Setting range Default Min. Attri.
F4.00
Protection function configuration
word
0...15
Bit0: Pressure sensor fail-
ure (PSF)
Bit1: Actual pressure moni-
toring
Bit2: p/Q max. command
limit
Bit3: Oil changing detection
0 - Run
F4.15
Maximum system pressure (warn-
ing)
0.0...[F4.16] bar 500.0 0.1 Stop
F4.16 Maximum pump pressure (error) [F4.15]...4,000.0 bar 1,000.0 0.1 Stop
F4.17
Maximum system pressure warning
time delay
0.0...6000.0 s 0.0 0.1 Run
F4.18
Maximum pump pressure error time
delay
0.0...6000.0 s 0.0 0.1 Run
Tab. 7-21:
Parameter list of pressure over limit detection
The detection of pressure feedback can be activated via bit1 of F4.00.
F4.15: When the feedback pressure goes beyond [F4.15] bar for [F4.17] s, the
warning (d0.88 = 1) will be triggered for the pressure feedback surpassing the
maximum system allowed pressure.
F4.16: When the feedback pressure goes beyond [F4.16] bar for [F4.18] s, the
failure (d0.89 = 1) will be triggered for the pressure feedback surpassing the
pump limit pressure, and then drive stops.
Fig. 7-21: F4.15 maximum system pressure warning