ā— Motor stops
If the motor stops and the feedback pressure is higher than [F4.10], the de-
tection function will check if the system pressure feedback keeps dropping
with decreasing rate higher than 1/[F4.11] bar/s, if the pressure drops slower
than this rate consistently for 2x[F4.11] seconds, a failure for sensor defect
will be signalled.
Fig. 7-20: Pressure sensor failure
FcP 5020 Bosch Rexroth AG
Block Diagram of Main Functions
DOK-RCON03-FCP5020****-QU04-EN-P
47/83