7.6 Quick Configuration For Rexroth MOT-FC_HOY Motor
When MOT-FC_HOY motor is used with FcP 5020 ASF application, saved motor
parameters can be loaded via F1.15 and F1.16. Please keep [F1.15]=1 for MOT-
FC_HOY motor, for third part motor please set [F1.15]=0 and set the motor pa-
rameter in EFC parameter group C1. For more information please reference EFC
5610 quick start guide (material number is R912005856).
Code Name Setting range Default Min. Attri.
F1.15 Motor type
0: Others
1: MOT-FC_HOY
1 - Stop
F1.16 Motor power level
0: No selection
1...5: Reserved
6: 1.5 kW
7: 2.2 kW
8: 3 kW
9: 4 kW
10: 5.5 kW
11: 7.5 kW
12: 11 kW
13: 15 kW
14: 18.5 kW
15: 22 kW
16: 30 kW
17: 37 kW
18: 45kW
19: 55 kW
20: 75 kW
21: 90 kW
0 - Stop
Tab. 7-5: Motor parameter list
Only change motor parameter by switching F1.16 to 1...21, when
[F1.15] = 1.
If [F1.15] = 0, no motor parameter will be changed by switching
F1.16 and the motor thermal model protection time constant
C1.74 is based on the EFC converter.
If the motor parameters from F1.15 / F1.16 are selected, the following parame-
ters in EFC converter will be changed automatically.
FcP 5020
Bosch Rexroth AG
Block Diagram of Main Functions
DOK-RCON03-FCP5020****-QU04-EN-P
27/83