8.6 Auto-modified EFC Parameters in FcP Initialization
Code Name Setting range Default Min. Attri.
E0.01 First run command source 0...2 1 - Stop
E0.02 Second frequency setting source 0...99 0 1 Stop
E0.08 Maximum output frequency 50.00...400.00 Hz 100.00 0.01 Stop
E0.09 Output frequency high limit [E0.10]...[E0.08] Hz 100.00 - Run
E0.17 Direction control
0: Forward / reverse
1: Forward only
2: Reverse only
3: Swap default direc-
tion
3 - Stop
E0.26 Acceleration time 0.1...6,000.0 s 0.5 0.1 Run
E0.27 Deceleration time 0.1...6,000.0 s 1.0 0.1 Run
E1.01 X2 input 0...46 34 - Stop
E1.61 Broken wire protection
0: Inactive
1: Warning
2: Error
0 - Stop
E2.15 Relay1 output selection 0...99 14 - Stop
E2.25 AO1 output mode
0: 0...10 V
1: 0...20 mA
1 - Run
Tab. 8-5: Auto-modified EFC parameter list