8.5 Group F4: System Protection and Pump Function Parameter
Code Name Setting range Default Min. Attri.
F4.00
Protection function configuration
word
0...15
Bit0: Pressure sensor failure
(PSF)
Bit1: Actual pressure moni-
toring
Bit2: p/Q max. command lim-
it
Bit 3: Oil changing detection
0 - Run
F4.03 Pump function configuration word
0...63
Bit0: Pump power limit
Bit1: Pump thermal protec-
tion
Bit2: Switch master to slave
Bit3: Two points / double
pump
Bit4: Pressure drop / over-
shoot compensation
Bit5: Activating myCro
0 - Stop
F4.06
Pressure sensor failure detection
threshold 1 (negative direction)
-5,000...0 rpm -1 1 Stop
F4.07
Pressure sensor failure detection
time 1 (negative direction)
0.1...100.0 s 10.0 0.1 Stop
F4.08
Pressure sensor failure detection
threshold 2 (positive direction)
0...5,000 rpm 200 1 Stop
F4.09
Pressure sensor failure detection
time 2 (positive direction)
0.1...100.0 s 10.0 0.1 Stop
F4.10
Pressure sensor detection thresh-
old (standby)
1.0...1,000.0 bar 5.0 0.1 Stop
F4.11
Pressure sensor detection period
(standby)
0.1...100.0 s 1.0 0.1 Stop
F4.15
Maximum system pressure (warn-
ing)
0.0...[F4.16] bar 500.0 0.1 Stop
F4.16 Maximum pump pressure (error) [F4.15]...4,000.0 bar 1,000.0 0.1 Stop
F4.17
Maximum system pressure warn-
ing time delay
0.0...6000.0 s 0.0 0.1 Run
F4.18
Maximum pump pressure error
time delay
0.0...6000.0 s 0.0 0.1 Run
F4.20 p/Q command soft start delay 0.0...1,000.0 s 0.0 0.1 Stop
FcP 5020 Bosch Rexroth AG
FcP 5020 Parameter List
DOK-RCON03-FCP5020****-QU04-EN-P
71/83