10
NICE - MIRIAM - CRISTAL - PRETTY - KRISS - MARY - TECNA - EVO
EN
top.
• It is forbidden to connect any other appliance (wood stoves, cooker hoods, boilers, etc...).
• The fume conduit must be placed at a distance of minimum 500 mm from ammable or heat-susceptible
components.
8.10 EXAMPLES OF CORRECT INSTALLATION
Fig. 8 - Example 1
LEGEND Fig. 8 page 10
1 Insulating material
2 Reduction from Ø100 to Ø80 mm
3 Inspection plug
4 Minimum safety distance = 0,5 mt
• Chimney ue installation Ø120 mm with an enlarged drilling for pipe transit.
Fig. 9 - Example 2
LEGEND Fig. 9 page 10
1 Insulating material
2 Inspection plug
3 Chimney inspection entrance
4 Minimum safety distance = 0,5 mt
5 Inclination ≥ 3°
6 Level section ≤ 1 mt