Each communicating device  in the Infinity Zone System has a four-pin
connector  labeled ABCD.  It  is  recommended  that  the  following  color
code be used when wiring each device:
A — Green = Data A+
B — Yellow = Data B-
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)
A03193
It is not mandatory that  the above color  code be  used, but each ABCD
connector in the system MUST be wired consistently.
NOTE:  Some  outdoor  units,  typically  those  with  multiple  compressor
stages, provide  their own  low-voltage  power  source and do not require
the “C” (24VAC common) and “D” (24VAC power) connections. See the
outdoor unit installation instructions for more information.
WARNING
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Before  installing,  modifying,  or  servicing  system,  the  main  electrical
disconnect switch must be in the OFF position. There may be more than
one disconnect switch. Lock out and tag switch with a suitable warning
label.