42
• Altitude: 0000 – 2000, US 2001 – 3000, CN 2100 – 4500, US 3001 –
4000, US 4001 – 5000, US 5001 6000, US 6001 – 7000, US 7001 –
8000, US 8001 – 9000, and US > 9000. Default = US 2001-3000
• Static Pressure selection: 0 to 10,000 ft. This value is used to correct
the static pressure readings the system performs. 
6.3.3.7.   Furnace Dehumidifier Drain
This  option  selects the  time  the  continuous  fan  turns  off  at  the  end  of
cooling in order to drain the indoor coil of water (Smart Evapt feature).
The  fan will only  be  turned  off  if  a dehumidify  demand  existed  at the
start of or during the cooling cycle.
• Dehumidify Drain Time: Adjustable from 5 to 60 minutes. Default =
15 minutes
6.3.3.8.   Furnace G Terminal
This setup option selects desired operation when the R-G circuit changes
state on the furnace control board depending on setup.
Under the function option, FAN turns on fan to selected fan speed when
G  terminal  is  energized.  SHUTDOWN  shuts  off  fan  and  equipment
when initiated.
After the selections are made, touch SAVE.
• Function: Disabled, Fan or Shutdown. Default = Disabled
• Fan Speed: Low, Med, or High. Default = Low
• Shutdown: 
– Normally Open
– Normally Closed
– The shutdown function may not be immediate. Blower off delays,
etc., will still be used. The shutdown is not intended for commercial
applications. If immediate shutdown is required, provision must be
made to remove power to indoor unit.