45
A13228
System in Control: The system will decide which stage should be
running to satisfy the heating demand.
High Heat: Temperature below which only the high stage of heating
will be energized.
Only Low Heat: The system will only run in low stage heating.
6.3.4.2. Cooling Lockout
Outside temperature below which cooling will not be provided. After the
selection is made, touch SAVE.
Cooling Lockout Temp: None, 45, 50 or 55 (°F). Default = None
NOTE: When simultaneous heating and cooling demand feature is on,
the cooling lockout shall be ignored.
6.3.4.3. Defrost Interval
Time interval at which defrost cycles can occur on a heat pump. AUTO
means the defrost interval is optimized by the outdoor control. After the
selection is made, touch SAVE.
Set Defrost Interval: 30, 60, 90, 120 minutes or AUTO. Default =
AUTO
NOTE: See Heat Pump Installation Instructions for Defrost Timing
Interval when using AUTO Defrost.