view  airflows  for  normal  air  conditioning  cooling  mode,  exit  the
CHECKOUT screen and apply a heating demand to the system.
• Low Cool Run Time: Selectable from 0 to 120 minutes. Default = 5
minutes
• High Cool Run Time: Selectable from 0 to 120 minutes. Default = 5
minutes
• Speed  (variable  speed  heat  pump  only):  Selectable  from  lowest
available to 100%. Default = lowest available as specified by variable
speed heat pump
6.4.7.   Humidifier
The humidifier can be exercised On and Off with this menu option. To
end the humidifier checkout, touch STOP.
• Humidifier Check: On or Off
6.4.8.   Ventilator
The ventilator can be exercised through all of its operating speeds with
this menu option. To end the ventilator checkout, touch STOP.
• Ventilator Check: High, Low or Off
NOTE:  This  option  may  NOT  be  available  with  the  ERVXXNVA
ventilator due to its simplified control design. 
6.4.9.   Zoning (If Applicable)
6.4.9.1.   Airflow Limits
Because  there  is  no  bypass  damper,  the  zone  airflow  limit  check  will
allow  the  installer  to  assess  the  airflow  noise  generated  by  the  system
providing  the  maximum  amount  of  airflow  to  each  zone.  Touch
AIRFLOW  LIMITS:  When  START  is  touched,  the  selected  zone’s
damper  will  fully  open,  all  others  will  close,  and  the  indoor  unit  will
provide  the maximum  airflow  for  that  zone  (as  selected  in  SETUP —
ZONING,  Airflow  Limits).  If  the  airflow  noise  is  objectionable,  the