• If  Simultaneous  Heat/Cool  is  turned  OFF,  Auto  changeover  time:
Adjustable from 5 to 120 minutes. Default = 30 minutes
NOTE: AUTO mode is intended to switch between Heating and Cooling
modes  based  on  temperature  demand. A  gradual  auto  transition  is  the
energy-conscious  default  that  will  satisfy  the  majority  of  customers.
Some  customers  might  have  significant  and  simultaneous  heating  and
cooling  demands  in  different  zones.  To  address  this  need,  a  special
simultaneous heating and cooling demand  auto mode  could  be  enabled
by  the  Installer.  The  simultaneous  heating  and  cooling  demand  auto
mode  will  result  in  higher  energy  usage  but  benefit  the  customer  with
greater comfort.
A160183_2
6.3.1.2.   Heat/Cool Deadband
The minimum difference enforced between heating and cooling desired
temperatures.  The  deadband  does  not  change  when  the  user  changes
between Fahrenheit (°F) and Celsius (°C). Ex: A 2° deadband will be 2°F
or 2°C and does not  change with  units, °F  and °C. This  can allow  one
setting to “push” the other to maintain this difference. When the correct
deadband is set, touch SAVE.
• Deadband: Adjustable from 0 to 6°. Default = 2°