• Smart Recovery: On or Off. Default = On
NOTE: The “Temperature Units Display” set-up section has been moved
to  the  Homeowner  Screens.  See  the  Owner’s  Manual  for  more
information.
6.3.2.   Fan Coil
First touch SETUP, then touch FAN COIL to set up the parameters for
the fan coil unit.
6.3.2.1.   Airflow
This option allows the installer to select the appropriate air flow based on
the  needs  of the  installation. The  QUIET  airflow  means  the minimum
cooling airflow that the system can safely run (typically 300 CFM/ton).
Use this setting if duct noise is a severe problem. Note that duct sweating
in high humidity  environments could  become  an issue at  low airflows.
The COMFORT airflow means airflow is varied depending on humidity
and  temperature  demand  settings.  This  selection  enables  the  full
dehumidify and comfort capabilities of the system. The EFF325 airflow
is a fixed airflow used to achieve specified ratings – no dehumidification
airflow reduction is performed. This is nominally 325 CFM/ton, but will
vary  if  a  2-stage  outdoor  unit  is  used.  The  EFF350  airflow  is  a  fixed
airflow used to achieve specified ratings – no dehumidification airflow
reduction is performed. This is nominally 350 CFM/ton, but will vary if a
2-stage outdoor unit is used. The MAX airflow is a fixed 400 CFM/ton.
No dehumidification airflow reduction is performed.
NOTE:  For  Geothermal  Heat  Pumps,  the  airflow  labels  have  been
changed  from  EFF325  and  EFF350  to  EFF1  and  EFF2,  respectively.
Nominal  geothermal  system  airflows  for  these  settings  tend  to  be
different than the typical 325 and 350 CFM/ton values.
The dehumidify airflow, when set to NORMAL, is allowed to adjust to a
minimum  to  satisfy the  dehumidification  call. When  set  to  HIGH,  the