6.4.1.   Electric Heat
If you have a fan coil with electric heaters, this menu item will allow the
heaters to be exercised. With self-identifying electric heaters, three stages
of  electric  heat  are  available  to  be  exercised  in  any  combination.
Non-identifying heaters will only provide one stage of heat; or perhaps
may  have  fixed-timed  staging.  See  the  instructions  provided  with  the
electric heat accessory. After the selections are made, touch START.
• Low Heat: Selectable from 0 to 120 minutes. Default = 5 minutes
• Medium Heat: Selectable from 0 to 120 minutes. Default = 5 minutes
• High Heat: Selectable from 0 to 120 minutes. Default = 5 minutes
6.4.2.   Furnace
Make sure the furnace is properly installed.
This option allows the furnace to be exercised. First, a low heat run time
and high heat run time are selected. The furnace will execute its ignition
start-up sequence. This sequence will be displayed  on the screen. After
the gas valve and blower motor turn on, the screen will show the current
operating  status  of  the  furnace.  After  the  selections  are  made,  touch
START.
• Low Heat: Selectable from 0 to 120 minutes. Default = 5 minutes
• High Heat: Selectable from 0 to 120 minutes. Default = 5 minutes