6.3.7.2.   Lockout Count
This setting controls the number of times within an hour that the HPS or
LPS  trips  before  the  Geo  HP  compressor  will  lockout  for  four  hours.
After the selection is made, touch SAVE.
• Lockout Count: 4 or 2
• Default = 2
A150180
6.3.7.3.   Brownout Override
This option  controls the low voltage brownout override function in the
Geo HP unit. After the selection is made, touch SAVE. 
• Brownout Override: Active or Inactive. Default = Inactive