6.3.4.4.   Low Ambient Cooling
Selecting  YES  will  enable  the  low  ambient  cooling  operation  in  the
outdoor  unit.  This  setting  is  only  available  with  compatible
communicating outdoor units and  with Cooling Lockout  set  to  NONE.
Low  ambient  kits  are  not  needed  with  many  communicating  outdoor
units. Refer to the outdoor unit Product Data or Installation Instructions
for more information. After the selection is made, touch SAVE.
• Low Ambient Cooling: Yes or No. Default = No
6.3.4.5.   Quiet Shift
This  option  turns  on  Quiet  Shift  function  in  1-stage  or  2-stage
communicating heat pumps. After the selection is made, touch SAVE.
NOTE: This option is not available with variable speed heat pumps nor
geothermal units.
• Quiet Shift: On or Off. Default = Off
6.3.4.6.   AC/Heat Pump RPM Max
Used  with  variable  capacity  heat  pumps,  this  option  clamps  the
operating  speed  of  the  heat  pump  to  this  maximum.  Used  to  reduce
operating noise while in high heating capacity. Reducing this value will
reduce the heating capacity of the heat pump. After the selection is made,
touch SAVE.
• AC Heat Pump Max RPM: Adjustable from 4500 – 7000. Default =
7000 RPM
6.3.4.7.   Defrost Fan Delay
Turns  on  the  outdoor  unit  fan  at  the  end  of  a  defrost  cycle  for
approximately 12 seconds. This helps to reduce any nuisance refrigerant
noise  caused  by  the  switching  reversing  valve.  This  setup  is  only
available  on  communicating  heat  pumps. After  the  selection  is  made,
touch SAVE.
• Defrost Fan Delay: Yes or No. Default = No