40
EFF1) airflow is  a fixed  airflow used  to achieve specified ratings – no
dehumidification airflow reduction is performed. This is nominally 325
CFM/ton, but will vary if a 2-stage outdoor unit is used. The EFF350 (or
EFF2  airflow  is  a fixed airflow  used  to  achieve  specified  ratings  – no
dehumidification airflow reduction is performed. This is nominally 350
CFM/ton,  but  will  vary  if  a  2-stage  outdoor  unit  is  used.  The  MAX
airflow is a fixed 400 CFM/ton. No dehumidification airflow reduction is
performed.
NOTE:  For  Geothermal  Heat  Pumps,  the  airflow  labels  have  been
changed  from  EFF325  and  EFF350  to  EFF1  and  EFF2,  respectively.
Nominal  geothermal  system  airflows  for  these  settings  tend  to  be
different than the typical 325 and 350 CFM/ton values.
The dehumidify airflow, when set to NORMAL, the airflow is allowed
to adjust to a minimum to satisfy the dehumidification call. When set to
HIGH, the minimum airflow during the dehumidify mode is increased to
reduce duct and register sweating. Also the  airflow increases minimum
airflow during normal cooling operation to help reduce duct sweating.
After the selections are made, touch SAVE.
• Cool: Quiet, Comfort, EFF325 (or EFF1), EFF350 (or EFF2), or Max.
Default = Comfort
• HP Heat: Comfort, EFF325  (or EFF1), EFF350 (or EFF2), or Max.
Default = Comfort
• Dehumidify: Normal or High. Default = Normal
6.3.3.3.   Furnace Staging
This option controls the staging of the furnace and selects the minimum
amount  of  time  low  stage  must  operate  before  high  stage  is  activated.
SYSTEM  setting  will  allow  the  Infinity  Zone  Control  to  determine
furnace  staging.  LOW  will  only  run  the  low  stage  of  furnace  heat.
LOW-MED will run the low and medium stages (2 stages of heat). MED
will  only  run  the  medium  stage  of  heat.  MED-HIGH  will  run  the