52
A12191
6.3.8.1.   Disable Zoning 
This  option  allows  the  installer  to  enable  or  disable  zoning. After  the
selection is made, touch SAVE.
• Disable Zoning: Yes or No. Default = No
6.3.8.2.   Zone Offsets
This  option  allows  actual  temperature  offset  for  each  zone,  allowing
calibration (or deliberate miscalibration) of each sensor. Use the Left (<)
or  Right  (>)  buttons  to  change  the  zone. After  the  selection  is  made,
touch SAVE.
• Temperature  Offset:  Adjustable  between  -5  to  5°F  (-3  to  3°C).
Default = 0°F
6.3.8.3.   Airflow Limits
Since a bypass damper is prohibited in this system, this setting is used to
select the maximum allowable noise/airflow relationship into each zone
based  on  air  noise  and  comfort  requirements.  LOW  means  100%  of
maximum  assessed  airflow;  MED-LOW  means  138%  of  maximum
assessed airflow; MEDIUM means 176% of maximum assessed airflow;
MED-HIGH means 214% of maximum assessed airflow; HIGH means
250%  of  maximum  assessed  airflow;  and  NO  LIMIT  means  the