36
minimum  airflow  during  the  dehumidify  mode  is  increased  to  reduce
duct and register sweating. Also the airflow increases minimum airflow
during normal cooling operation to help reduce duct sweating.
After the selections are made, touch SAVE.
• Cooling Airflow:  Quiet,  Comfort,  EFF325  (or  EFF1),  EFF350  (or
EFF2), or Max. Default = Comfort
• Heating Airflow: Comfort, EFF325 (or EFF1), EFF350 (or EFF2), or
Max. Default = Comfort
• Dehumidify Airflow: Normal or High. Default = Normal
6.3.2.2.   Altitude
• Static Pressure selection: 0 to 10,000 ft. This is used to correct the
static pressure readings the system performs.
6.3.2.3.   Dehumidification Options
The  Dehum  Drain  Time  (Smart  Evap™  feature)  option  turns  off  the
continuous fan at the end of cooling for fifteen minutes in order to drain
the indoor coil of water. The fan will only be turned off if a dehumidify
demand existed at the start of or during the cooling cycle.
The Electric Reheat option (fan coils, only) enables the electric heat to be
used  while  cool-to-dehumidify  is  running.  This  will  allow  the
cool-to-dehumidify  function  to  run  longer,  greatly  improving  humidity
control  in  cooling  mode.  Accumulated  electrical  energy  used  while
reheating (in kilowatt-hours) is shown on the Fan Coil Run Hours screen
and can be reset there. This option is only available with fan coil systems.
Self-identifying  (staging)  heaters  provide  the  best  performance  for
re-heat  dehumidification.  For  reheat  applications,  9kW  heaters  provide
the  best  performance.  The  reheat  algorithm  functions  along  with  the
overcool  algorithm.  If  the  room  temperature  is  low  enough  that
overcooling is not allowed, reheat will not be allowed. Overcooling must
happen before the electric heaters are energized.
After the selections are made, touch SAVE.