28
measurement. The system will then close all zones and open one zone at
a time, taking a static pressure measurement for each zone.
The system will then close all  zones  and take a  pressure measurement,
getting a value for the duct leakage up to and through the dampers. With
these static pressure measurements, the system will calculate the relative
size of each zone as well as the percent leakage through the dampers at
the end of the process, the display will show the relative size of each zone
duct.
If  the  Infinity  System  Control detects  an  error  (damper  not moving  or
damper wired backwards), it will perform the duct assessment again. If it
still  detects  a  damper  problem,  it  will  default  the  measurements  into
equal  sizes,  with  10%  leakage,  and  display  the  zone  number  for  the
suspected zone damper.
NOTE:  The  daily  duct  assessment  will  occur  even  if  static  pressure
monitoring  is  disabled.  This  is  done  to  ensure  that  the  system  will
continue to provide proper airflow for all installed equipment, since duct
system  changes  may  occur  at  any  time,  such  as  opened  or  closed
registers.
After the duct assessment is complete, touch NEXT.
6.   Service Menu
The Service  menus contain  a set of vital  information. This information
enables the installer or service person  to  view a summary  of what has
been  installed,  etc.  This  information  is  not  covered  in  the  Owner’s
Manual.
To enter service menus, touch menu, then touch and hold the SERVICE
icon, for  at least  ten seconds, until  the icon  turns green. The following