Alternate space temperature sensor
Carrier Sensors 15
User Options
100 Firmware version
101 Temperature scale
00 = °F
01 = °C
102 Temperature Offset (Sensor Trim) °F
00 = -5
01 = -4
02 = -3
03 = -2
04 = -1
05 = 0 (typical)
06 = 1
07 = 2
08 = 3
09 = 4
10 = 5
103 Normal Setpoint Display
00 to 09 = Do Not Use
Offset Setpoint Display
10 = -02 to 02°F (-02 to 02°C)
11 = -03 to 03°F (-03 to 03°C)
12 = -05 to 05°F (-05 to 05°C)
104 Keep at 00
105 Setpoint Lockout
00 = Disable Lockout
01 = Enable Lockout
106 Keep at 00
107 Keep at 00
108 Display Mode
00 = Normal
01 = Setpoint Only
109 Keep at 00
Field Service Options
126 Setpoint mode
00 = Use option page 103 setting
01 = Display single offset setpoint
02 = Display Heat/Cool setpoints
03 = Display Heat/Cool setpoints w/Occupied
(Occupied icon is shown in setpoint display mode.)
127 Setpoint feedback
00 = Disable feedback
01 = Enable Occupied/unoccupied feedback
02 = Enable Heat/Cool feedback