EasyManua.ls Logo

Carver C43 - System Organization

Default Icon
140 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 3Section 3
42 4327 • X5 04/2015
Connect metallic housings or enclosures of installed electrical appliances to the protective conductor system in the craft
(green or green with a yellow stripe conductor).
Use double-installed or grounded (earthed) electrical appliances.
If reverse polarity indicator is activated, do not use electrical system. Correct the polarity fault before activating the electrical
system on the craft.
Test the AC main breakers on a monthly basis by pressing the “T” on the breaker (CE only).
If tripping occurs:
1. Unplug all appliances.
2. Reset the switch.
3. Individually plug in each appliance until the safety switch trips to determine the faulty appliance.
If the safety switch does not trip with individual appliances, the circuit may be over-loaded.
If the safety switch trips with no appliances connected, the installation cabling may be damaged. Consult an electrician.
SYSTEM ORGANIZATION
NORTH AMERICA/PACIFIC RIM
OPTIONAL (NA/PR ONLY, NORTHERN AIR CONDITIONING PACKAGE) DUAL 120 VOLT, 30 AMP, 60 HERTZ
SHORE 1: The SHORE 1 (30 amp) circuit on the AC electrical panel provides power to all the AC equipment except the air
conditioning system. SHORE 1 is congured as 120 volts, 60 Hz. See the breakers on the AC panel for a list of installed
items controlled by the SHORE 1 circuit.
SHORE 2: The SHORE 2 (30 amp) circuit, located on the AC electrical panel, provides power to all the AC components
listed on the SHORE 2 column of circuit breakers on the AC control center. SHORE 2 is congured as 120 volts, 60 Hz. See
the breakers on the AC panel for a list of installed items controlled by the SHORE 2 circuit.
Dual 120 Volt,
30 Amp, 60 Hertz

Table of Contents