Index Name Description Type
25L bNoEPC Flag (true or false) that indicates if module has an AC input (EPC) or not U8
26 wPoutNominalW Nominal output power (W) U16
27 wPoutNominalVA Nominal output power (VA) U16
28 wVinNominalAC Nominal AC input voltage (0.1V) U16
29 wVinNominalDC Nominal DC input voltage (0.1V) U16
30 wVinNominalFreqAC Nominal AC frequency (0.1Hz) U16
Phase table (0x0640)
The following table described represents the information that can be retrieved regarding a particular phase. Maximum
amount of phase is set to 8. Each of them is identified by a label ranging from 1 to 8.
BASE ADDRESS: 600(0x0640) + 27*(Phase label – 1).
Index Name Description Type
0H bRatioAvailableW Ratio between output load and available power in watts (%) U8
0L bRatioAvailableVA Ratio between output load and available power in VA (%) U8
1H bRatioInstalledW
Ratio between output load and installed power (Nb modules –
redundancy) in watts (%)
U8
1L bRatioInstalledVA
Ratio between output load and installed power (Nb modules –
redundancy) in VA (%)
U8
2 wVout Output voltage value (0.1V) U16
3 wIout Output current value (0.1A) U16
4H bNbOndCfg Number of modules configured in the phase U8
4L bRedundancy Amount of redundancy configured in the phase U8
5 wACOutFreq AC output frequency value (0.1Hz) U16
6 lPinDC DC input power value (W) U32
8 lPinACW AC input power value (W) U32
10 lPinACVA AC input power value (VA) U32
12 lCurrentPowerInVA Output power value (VA) U32
14 lCurrentPowerInW Output power value (W) U32
16 lInstalledPowerInW Installed power value (W) U32
18 lInstalledPowerInVA Installed power value (VA) U32
20 lAvailablePowerInW Available power value (W) U32
22 lAvailablePowerInVA Available power value (VA) U32
24H bNbInvSeen Number of module seen by T2S ETH in that phase U8
24L bNbInvOK Number of modules that are delivering output in the phase U8
25H bNbInvMO Number of modules manually off in the phase U8
25L bNbInvKO
Number of modules that are not delivering output due to a failure in the
phase
U8
80 – Monitoring T2S - ETH User Manual – v1.4