Total
Power
Tray
N+N Redundancy Mode
in Watts (with Feed Loss)
N+1 Redundancy Mode in
Watts (with Single Supply
Loss)
Combined Mode in Watts
(No redundancy)
Total Power
Supply
3
2
19,80035,20039,6009
22,00039,60044,00010
24,20044,00048,40011
26,40048,40052,80012
•
1
Cisco 8804 router supports 2 power trays.
•
2
Cisco 8808 and Cisco 8812 routers support 3 power trays.
Note
Total
Power
Tray
N+N Redundancy Mode
in Watts (with Feed Loss)
N+1 Redundancy Mode in
Watts (with Single Supply
Loss)
Combined Mode in Watts
(No redundancy)
Total Power
Supply
4
3
28,60052,80057,20013
30,80057,20061,60014
33,00061,60066,00015
35,20066,00070,40016
5
3
37,40070,40074,80017
39,60074,80079,20018
41,80079,20083,60019
44,00083,60088,00020
6
3
46,20088,00092,40021
48,40092,40096,80022
50,60096,800101,20023
52,800101,200105,60024
3
Power Tray 4, 5 and 6 are applicable for Cisco 8818 Router.
Note
Hardware Installation Guide for Cisco 8800 Series Routers
9
Cisco 8800 Series Routers Overview
Maximum Power Available to the Router