Appendix A Technical Specifications
Chassis Airflow
64 to 71ºF (18 to 22ºC) 1459 89 1548
73 to 80ºF (23 to 27ºC) 1459 95 1554
82 to 89ºF (28 to 32ºC) 1459 124 1583
91 to 98ºF (33 to 37ºC) 1583 153 1736
100 to 107ºF (38 to 42ºC) 1713 180 1893
109 to 116ºF (43 to 47ºC) 2158 195 2353
118 to 125ºF (48 to 52ºC) 2461 207 2668
127 to 136ºF (53 to 58ºC) 2770 207 2977
> 136ºF (58ºC) 2770 207 2977
Table A-17 Airflow for a Fully Configured Cisco Nexus 7018 Switch (continued)