ECON-4, SW version 1.4 rev.1, ©ComAp – March 2016 Draft 41
ECON-4 Reference guide.pdf
InitStart dose [%]
Initial position of the actuator during start.
Step: 1 %
Range: 1 – 100 %
MaxStart dose [%]
Maximum position of the actuator during start.
Step: 1 %
Range: 1 – 100 %
Fuel ramp time [s]
Time the actuator needs to move from the InitStart dose to MaxStart dose.
Step: 1 s
Range: 1 – 100 s
When the engine speed rises above Starting RPM, ECON-4 activates PID speed regulation loop. The
Speed reference rises from Starting RPM to Idle RPM with speed ramp defined by setpoint RPM
StartRamp.