ECON-4 1.4.0 Global Guide
17
4.4.6 Analog output
ECON-4 has one analog output configurable to 0-10V or 0-20mA range by jumper setting see in table below. If
configured to 0-20mA range, output works as an active current source. The analog output function is fix (copy of
the value sent to ACT output - GAS DOSE). Analogue output range is fully programmable in range 0-10V or 0-
20mA see setpoints: Analog settings: AOUT 0%and AOUT 100%.
Range Recommended wiring Output Terminals Jumpers
0-20
mA
AOUT
S6.1
S6.2
P6 - 20 mA
0-10 V AOUT
S6.1
S6.2
P6 - 10 V
Gas Dose (S6.1)
Output signal corresponds to actuator requested position. The limits are fully scaleable in range 0-10V (0-
20mA).
E.g an actuator with input 4-20mA is used, the AOUT2 range setpoints should be adjusted in the following way: