8.1.3 Group: Engine StartGroup: ECON4-EngRPM
Setpoint group Engine RPM Related FW
1.4.0
configured ECON-4 extension
module
Range [units] Start RPM - Nominal RPM
Default value 1000 RPM Force value NO
Step 1 RPM
Comm object 7186 Related applications ALL
Description
Engine idle speed.
Idle RPM
6 back to List of setpoints
Setpoint group Engine RPM Related FW
1.4.0
configured ECON-4 extension
module
Range [units] 0 - 2500 [RPM]
Default value 1500 RPM Force value NO
Step 1 RPM
Comm object 7187 Related applications ALL
Setpoint visibility Always
Description
Nominal engine speed.
Nominal RPM
6 back to List of setpoints
Setpoint group Engine RPM Related FW
1.4.0
configured ECON-4 extension
module
Range [units] 0 - 2500 [RPM]
Default value 1800 RPM Force value NO
Step 1 RPM
Comm object 7168 Related applications ALL
Setpoint visibility Always
Description
Maximum acceptable speed of the engine. If the actual engine speed is higher, ECON-4 immediately closes
the actuator. Normal function is restored after detection of zero engine speed.
Overspeed
6 back to List of setpoints