Page #47 background image
ECON-4 1.4.0 Global Guide
47
Setpoint group Engine RPM Related FW
1.4.0
configured ECON-4 extension
module
Range [units] 32 - 400 [-]
Default value 256 Force value NO
Step 1
Comm object 7188 Related applications ALL
Setpoint visibility Always
Description
Number of teeth on the engine gear for the pick-up.
Gear teeth
6 back to List of setpoints
Setpoint group Engine RPM Related FW
1.4.0
configured ECON-4 extension
module
Range [units] 0 - 100 [s]
Default value 10 s Force value NO
Step 1 s
Comm object 7169 Related applications ALL
Setpoint visibility Always
Description
Define how fast changes the requested engine speed during transition from Idle RPM (page 46) to Nominal
RPM (page 46) and vice versa. Idle-Nom ramp is directly time that the ramp needs to go from Idle RPM (page
46) to Nominal RPM (page 46) and vice versa. The ramping speed is the same for both up and down
directions.
Idle-Nom ramp
6 back to List of setpoints