ECON-4 1.4.0 Global Guide
48
Setpoint group Engine RPM Related FW
1.4.0
configured ECON-4 extension
module
Range [units] 1.0 - 100.0 [s]
Default value 50 s Force value NO
Step 1.0 s
Comm object 7170 Related applications ALL
Setpoint visibility Always
Description
Define how fast changes the requested engine speed if the binary inputs SPEED UP or SPEED DOWN are
active. BI Speed ramp is actually time that the ramp needs to go from Nominal RPM (page 46) - 8%
toNominal RPM (page 46) + 8% and vice versa. The ramping speed is the same for both up and down
directions.
BI Speed ramp
6 back to List of setpoints