ECON-4 1.4.0 Global Guide
58
Setpoanticip
group
Main PID Related FW
1.4.0
configured ECON-4 extension
module
Range [units] 0.0 - 100.0 [%]
Default value 0% Force value NO
Step 0.1 %
Comm object 11102 Related applications ALL
Setpoanticip
visibility
WinScope only
Description
Governor is equipped by load anticipation feedback, which helps to keep stable speed in case of fast load
changes. In the case of load jump forces the ECON-4 governor output (Actuator lever) by jump according to
Load anticip setting.
Engine load value can be received via physical Analog input S3.2 ACTIVE POWER as 0 to 10V or 20 mA
signal (if setpoanticip Speed request=BIN or ANA) or via CAN bus in the case of communication to IS-NT
controller (if setpoanticip Speed request=DATA). In such case follow this configuration in GenConfig: /
I/O Analog outputs ECON-4 AOUT1 = Gener values Act.power rel.
In the configuration choose option Normalize YES and resolution adjust to 0,1
There is 5 different setpoanticips Load anticip:
Load anticip 1
Load anticip 2
Load anticip 3
Load anticip 4
For more information about Load anticip setting please see Load 1 (page 59).
Load anticip
6 back to List of setpoints

Table of Contents

Other manuals for ComAp ECON-4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp ECON-4 and is the answer not in the manual?

ComAp ECON-4 Specifications

General IconGeneral
BrandComAp
ModelECON-4
CategoryController
LanguageEnglish

Related product manuals