EasyManuals Logo

ComAp ECON-4 User Manual

ComAp ECON-4
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #70 background imageLoading...
Page #70 background image
ECON-4 1.4.0 Global Guide
70
Setpoint group ActType 1,2,3,4 Related FW 1.4.0
Range [units] 0.0 100.0 [%]
Default value 100% Force value NO
Step 0.1 %
Comm object 11112 Related applications ALL
Setpoint visibility WinScope only
Description
Actuator Overload protection limit.
Act MaxCur
6 back to List of setpoints
Setpoint group ActType 1,2,3,4 Related FW 1.4.0
Range [units] 0.0 300.0 [s]
Default value 5 s Force value NO
Step 0.1 s
Comm object 11113 Related applications ALL
Setpoint visibility WinScope only
Description
Actuator Overload protection limit delay.
ActmaxCurDel
6 back to List of setpoints
Setpoint group ActType 1,2,3,4 Related FW 1.4.0
Range [units] 0.0 100.0 [%]
Default value 40% Force value NO
Step 0.1 %
Comm object 11114 Related applications ALL
Setpoint visibility WinScope only
Description
Reduced actuator current when overload protection was activated.
Act ReducedCur
6 back to List of setpoints