EasyManuals Logo

ComAp ECON-4 User Manual

ComAp ECON-4
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #73 background imageLoading...
Page #73 background image
ECON-4 1.4.0 Global Guide
73
6 back to List of setpoints
Setpoint group Analog sensors Related FW
1.4.0
configured ECON-4 extension
module
Range [units] 0 100 %
Default value 0 % Force value NO
Step 1 %
Comm object 11643 Related applications ALL
Setpoint visibility WinScope only
Description
Analogue output low limit signal definition.
AOUT 0
6 back to List of setpoints
Setpoint group Analog sensors Related FW
1.4.0
configured ECON-4 extension
module
Range [units] 0 100 %
Default value 100 % Force value NO
Step 1 %
Comm object 11645 Related applications ALL
Setpoint visibility WinScope only
Description
Analogue output high limit signal definition.
AOUT 100
6 back to List of setpoints
Setpoint group Analog sensors Related FW
1.4.0
configured ECON-4 extension
module
Range [units] 0,40 Fdb1 100 pos.V
Default value 01.76 V Force value NO
Step 0.01 V
Comm object 11662 Related applications ALL
Setpoint visibility WinScope only
Description
Feedback fully closed position voltage. Connect the position feedback to the ECON-4 terminals. Keep the
actuator lever in fully closed position and measure a dc voltage between the terminals S2.1 and S2.3. This
voltage put as this setpoint value.
FBD 0 pos
6 back to List of setpoints

Table of Contents

Other manuals for ComAp ECON-4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp ECON-4 and is the answer not in the manual?

ComAp ECON-4 Specifications

General IconGeneral
BrandComAp
ModelECON-4
CategoryController
LanguageEnglish

Related product manuals