ECON-4 1.4.0 Global Guide
73
6 back to List of setpoints
Setpoint group Analog sensors Related FW
1.4.0
configured ECON-4 extension
module
Range [units] 0 100 %
Default value 0 % Force value NO
Step 1 %
Comm object 11643 Related applications ALL
Setpoint visibility WinScope only
Description
Analogue output low limit signal definition.
AOUT 0
6 back to List of setpoints
Setpoint group Analog sensors Related FW
1.4.0
configured ECON-4 extension
module
Range [units] 0 100 %
Default value 100 % Force value NO
Step 1 %
Comm object 11645 Related applications ALL
Setpoint visibility WinScope only
Description
Analogue output high limit signal definition.
AOUT 100
6 back to List of setpoints
Setpoint group Analog sensors Related FW
1.4.0
configured ECON-4 extension
module
Range [units] 0,40 Fdb1 100 pos.V
Default value 01.76 V Force value NO
Step 0.01 V
Comm object 11662 Related applications ALL
Setpoint visibility WinScope only
Description
Feedback fully closed position voltage. Connect the position feedback to the ECON-4 terminals. Keep the
actuator lever in fully closed position and measure a dc voltage between the terminals S2.1 and S2.3. This
voltage put as this setpoint value.