4.6.4 Dimensions
Unit is 35 mm DIN rail mounted.
4.6.5 Technical data
Dimension (W×H×D) 157×55×95 mm (6.18´×2.2´×3.7´)
Interface to controller Direct mounted (SUB25)
Primary voltage Ph-Ph
3×400 VAC/50Hz (3×480 VAC/60 Hz)
3×600 VAC/50Hz (3×720 VAC/60 Hz)
Secondary voltage Ph-N
230 V AC (3×277 VAC/60 Hz), 5 VA
173 V AC (3×208 VAC/60 Hz), 5 VA
Primary/secondary Phase shift
±
±
Conversion accuracy
± 1.5% at 50Hz
± 3.0% at 50Hz
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 70 °C