Setpoint visibility Always
Description
“Pulses per liter” constant of fuel flow sensor connected to the second pulse input of IL-NT-FCM module.
By setting this constant, the propper counting of FuelAutrefTot value in values group Fuel Mgmt is
provided, showing the total amount of fuel refilled through this sensor.
4.10.5 Wiring
4.10.6 Technical data
Dimension (W×H×D) 66×34×16 mm (2.6´×1.34´×0.63´)
Interface to controller Direct mounted
Pulse input Max 2kHz, input voltage 9 to 27Vpp
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 70 °C
6 back to IL-NT-FCM