EasyManuals Logo
Home>ComAp>Controller>Inteli Mains NTC BaseBox

ComAp Inteli Mains NTC BaseBox User Manual

ComAp Inteli Mains NTC BaseBox
141 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #55 background imageLoading...
Page #55 background image
Communication Guide, ©ComAp March 2014 55
IGS-NT Communication Guide 03-2014.pdf
Controllers
IG-NT
IG-NTC
IS-NT-BB
IM-NT
Connection applicable
YES
YES
YES
YES
Physical port
RS485 (1)
RS485 (1)
RS485 (1)
RS485 (1)
It is possible to connect up to 3 InteliVision 5 displays to RS485(1) terminal Link.
Hint:
Connection InteliVision 5 to IG/IS-NT controllers is described in InteliVision 5 Reference Guide.pdf
Controller setup
(Setpoints/Comms settings group)
RS485(1) conv. = DISABLED
Comms extension - I-LB+ Local bridge
Description
I-LB+ is communication modules for communication with all devices connected to CAN(2) bus. I-LB+
is successors of the IG-MU unit designed to be used with IG/IS controllers. It therefore provides
additional communication port and higher communication speed. Speed for direct/modem connection
can be up to 57600 bps (IG-MU only 19200 bps). I-LB / I-LB+ can be connected with PC via USB,
RS232 or RS485. I-LB is without USB port, I-LB+ is with USB port (speed ≈ 115200 bps).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp Inteli Mains NTC BaseBox and is the answer not in the manual?

ComAp Inteli Mains NTC BaseBox Specifications

General IconGeneral
BrandComAp
ModelInteli Mains NTC BaseBox
CategoryController
LanguageEnglish

Related product manuals