Communication Guide, ©ComAp – March 2014 55
IGS-NT Communication Guide 03-2014.pdf
It is possible to connect up to 3 InteliVision 5 displays to RS485(1) terminal Link.
Hint:
Connection InteliVision 5 to IG/IS-NT controllers is described in InteliVision 5 Reference Guide.pdf
Controller setup
(Setpoints/Comms settings group)
RS485(1) conv. = DISABLED
Comms extension - I-LB+ Local bridge
Description
I-LB+ is communication modules for communication with all devices connected to CAN(2) bus. I-LB+
is successors of the IG-MU unit designed to be used with IG/IS controllers. It therefore provides
additional communication port and higher communication speed. Speed for direct/modem connection
can be up to 57600 bps (IG-MU only 19200 bps). I-LB / I-LB+ can be connected with PC via USB,
RS232 or RS485. I-LB is without USB port, I-LB+ is with USB port (speed ≈ 115200 bps).