Setpoint group Engine parameters Related FW 2.5.0
Range [units] 0 .. 600 [s]
Default value 0 s -
Step 1 s
Comm object 15987 Related applications N/A
Description
Defines the shortest time of LBO Preheat activation prior to engine start reached when the measured
temperature is PreheatTemp1 (page 115) or higher. See description of PREHEAT (PAGE 201).
PreheatTime1
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] PreheatTemp1 (page 115) .. 600 [°C]
Default value 0 °C -
Step -
Comm object 15986 Related applications N/A
Description
Defines the temperature, at which the LBO Preheat activates for the shortest time prior to engine start. See
description of PREHEAT (PAGE 201).
PreheatTemp2
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] 0 .. 600 [s]
Default value 0 s -
Step -
Comm object 15988 Related applications N/A
Description
Defines the longest time of the LBO Preheat activation prior to engine start reached when the measured
temperature is PreheatTemp2 (page 116) or lower. See description of PREHEAT (PAGE 201).
PreheatTime2