ID-FLX Lite Global Guide
168
Setpoint group Date/Time Related FW 2.5.0
Range [units] [DD:MM:YYYY]
Default value -
Step -
Comm object 24553 Related applications
Description
Actual date.
Date
6 back to List of setpoints
Setpoint group Date/Time Related FW 2.5.0
Range [units] NoFunc, AutoRun, AutoRegCMP, AutoBatt, AutoStop [-]
Default value No Func -
Step -
Comm object 11660 Related applications
Description
No Func
Operates just corresponding TIMER1 (PAGE 219) according the TIMER1 (PAGE 219)
setting, see Timer1repeat (page 169), Timer1 ON time (page 169), Timer1Duration
(page 169). Function operates in all OFF-MAN-AUT modes. Default state.
AutoRun
Engine automatically starts and stops in AUT mode (similar to REM START/STOP (PAGE
189), the same record in the history) according the TIMER1 (PAGE 219) setting.
AutoRegCMP
Start and stop engine in AUT mode according to the SPEEDSWITCH (PAGE 220) - see Reg
CMP Input (page 133). The comparator function (output) works opposite when Reg
CMP On (page 133) < Reg CMP Off. The Timer1repeat (page 169), Timer1 ON time
(page 169), Timer1Duration (page 169) settings are not important in this case.
AutoBatt
Engine starts when actual Battery voltage < Batt undervolt (page 145) + Batt volt del
(page 145) and stays running for Timer1Duration (page 169). Function operates in AUT
mode.
AutoStop
Engine is switched from AUT to MAN and stopped or stopped from MAN mode (like by
STOP button) when engine runs longer then Timer1Duration (page 169) on actual RPM
less or equal Idle speed (page 118) + 5% (fix limit). Function is not active during engine
start.
Timer1Function
6 back to List of setpoints