ID-FLX Lite Global Guide
170
Setpoint group Date/Time Related FW 2.5.0
Range [units] No Func, AutoRun, AutoRegCMP, AutoBatt, AutoStop [-]
Default value No Func -
Step -
Comm object 11661 Related applications
Description
No Func
Operates just corresponding TIMER2 (PAGE 219) according the TIMER2 (PAGE 219)
setting, see Timer2repeat (page 171), Timer2 ON time (page 171),
Timer2Duration (page 171). Function operates in all OFF-MAN-AUT modes.
Default state.
AutoRun
Engine automatically starts and stops in AUT mode (similar to REM START/STOP
(PAGE 189), the same record in the history) according the TIMER2 (PAGE 219)
setting.
AutoRegCMP
Start and stop engine in AUT mode according to the SPEEDSWITCH (PAGE 220) - see
Reg CMP Input (page 133). The comparator function (output) works opposite
when Reg CMP On (page 133) < Reg CMP Off (page 134). The Timer2repeat
(page 171), Timer2 ON time (page 171), Timer2Duration (page 171) are not
important in this case.
AutoBatt
Engine starts when actual Battery voltage < Batt undervolt (page 145) + Batt volt
del (page 145) and stays running for Timer2Duration (page 171). Function
operates in AUT mode.
AutoStop
Engine is switched from AUT to MAN and stopped or stopped from MAN mode (like
by STOP button) when engine runs longer then Timer2Duration (page 171) on
actual RPM less or equal Idle speed (page 118) + 5% (fix limit). Function is not
active during engine start.
Timer2Function
6 back to List of setpoints